Certification Record
LC1234495
MTU Maintenance Canada Ltd.
2023-08-08
British Columbia
Canada
Fuel Return Valve Test Stand
21.180, 29.260.20
- Fuel Return Valve test Stand and Pumping Skid
- Rating:
- Class I, Division 1, Group D, T2A
- +15°C to +40°C
- XP and Type X Purge
- Test Stand: 110Vac, 1 Phase, 60Hz, 15A
- Pumping Skid: 600Vac, 3 Phase, 60Hz, 60A
- Serial Nos.:
Serial Number Label Applied MTU 1220 test stand – 12783 C-20033 MTU 1220 pumping skid – 12783 C-20034
- CSA-C22.2 No. 61010-1-12 (R2017)
- CSA C22.2 No. 30:20
- NFPA 496:2021
- An explosionproof conduit seal shall be installed as close as practicable to, but not more than 450 mm (18 in.) from, the Explosion proof and pressurized enclosure.
General Note:
- Project no.: 21647
- LC Unit Verification Report no.: 11.03.21647-1 Rev.0
- LC Unit Verification Certificate no.: LC21647-1