LC Clients

Certification Record

LC1227412
H2Scan Corporation
2023-08-17
California
United States
Barrier P/N 50000021, HY-ALERTA Model 1600 Series, HY-OPTIMA Model 1700 and 1700B Series
29.260.20
  • IS Shunt Safety Assembly
  • Model: Barrier P/N 50000021 (To be used to limit power to the HY-ALERTA Model 1600 Series and HYOPTIMA Model 1700 and 1700B Series to an intrinsically safe level)
  • Ratings:
    • [Ex ib] IIC Gb (CSA rating)
    • Class I Zone 1 [AEx ib] IIC Gb (UL rating)
    • Electrical parameters:
      • Um = 250 V
      • Uo = 11.5 Vdc
      • Io = 3.27 Adc
      • Po = 9.41 W
      • Ci = 0
      • Li = 0
      • Co = 1.64uF
      • Lo = 3.3uH
      • Lo/Ro = 29 μH/ohms
  • Process Monitor
  • Model: HY-ALERTA Model 1600 Series & HY-OPTIMA Model 1700 and 1700B Series (to be used with associated IS Shunt Safety Assembly)
  • Ratings:
    • Input: 5 – 28Vdc (10Vdc nominal), 10W;
    • Output: 4 – 20mA

For units with sensing element intended to be used in Zone 0:
– Sensor ratings:

  • Ex ia II (H2) T3 Ga (CSA rating)
  • Class I Zone 0 AEx ia II (H2) T3 Ga (UL rating)
  • Class I Division 1 Group B T3 (CSA & UL rating)

– Analyzer ratings:

  • Ex db+db IIB T3 Ga (CSA rating)
  • Class I Zone 0 AEx db+db IIB T3 Ga (UL rating)
  • Class I Division 1 Group CD T3 (CSA & UL rating)

For units with sensing element intended to be used in Zone 1

– Sensor ratings:

  • Ex ib II (H2) T3 Gb (CSA rating)
  • Class I Zone 1 AEx ib II (H2) T3 Gb (UL rating)
  • Class I Division 2 Group B T3 (CSA & UL rating)

– Analyzer ratings:

  • Ex db IIB T3 Gb (CSA rating)
  • Class I Zone 1 AEx db IIB T3 Gb (UL rating)
  • Class I Division 2 Group CD T3 (CSA & UL rating)

The maximum intrinsically safe input and output parameters:

  • J1 Pins 2 & 3 (power supply)
  • Ui = 11.5 V
  • Ii = 3.27 A
  • Pi = 9.41 W

The equivalent parameters are:

  • CI = 0
  • LI = 0
  • J1 Pins 4 & 5 (4-20 mA loop)
  • UI = 26.7 V
  • Ii = 91 mA
  • Pi = 0.611 W

The equivalent parameters are:

  • CI = 68.2 nF
  • LI = 0
  • J2 Pins 1 & 2 and 3 & 4 (Rx and Tx)
  • UI = 3.7 V
  • Ii = 225 mA
  • Pi = 206 mW

The equivalent parameters are:

  • CI = 0
  • LI = 0
  • Uo = 5.9 V
  • Io = 238 mA
  • Po = 0.35 W
  • Co = 1000 μF
  • Lo = 2.5 mH
  • Lo/Ro = 404 μH/ohms

 

IS Shunt Safety Assembly

  • CAN/CSA C22.2 No. 60079-0:19 / UL 60079-0 (Ed. 7)
  • CAN/CSA C22.2 No. 60079-11:14 (R2018) / UL 60079-11 (Ed. 6)
  • CAN/CSA C22.2 No. 61010-1A-12 / UL 61010-1 (Ed. 3)

Process Monitor

  • CAN/CSA C22.2 No. 60079-0:19 / UL 60079-0 (Ed. 7)
  • CAN/CSA C22.2 No. 60079-1:16 / UL 60079-1 (Ed. 7)
  • CAN/CSA C22.2 No. 60079-11:14 (R2018) / UL 60079-11 (Ed. 6)
  • CAN/CSA C22.2 No. 60079-26:16 / UL 60079-26 (Ed. 3)
  • CAN/CSA C22.2 No. 61010-1A-12 / UL 61010-1 (Ed. 3)
  • None

General Note:

  • Project no.: 18552/18552A
  • LC Certificate no.: LC20CA18552-1
  • LC Listing report no.: 11.00.9001-1_Rev.4
    • Rev.1 – LC Listing report no. 9001-1S_Rev.1 under the project 9001
    • Rev.2 – LC Certificate no. 9001-1S_Rev.2 under the project LV-14007
    • Rev.3 – LC Certificate no. 9001-1S_Rev.3 under the project 12618
    • Rev.4 – LC Certificate no. LC20CA18552-1 under the project 18552/18552A
      – Refer to the listing report no. 11.00.9001-1_Rev 4.
      – Note that further revision will be under the certificate no. LC20CA18552-1
Go to Top