Certification Record
LC1236447
Realtime Automation Inc.
2024-01-03
Oklahoma
United States
25972XP followed by 3 or 4 & 25972XP followed by 1, 2, 5 or 8
29.260.20, 21.180, 29.240.30
- Rotary Actuators
- Model: 25972XP followed by 3 or 4;
- Class 2 Power Supply at 24VDC, 1.5A
- 24 VDC@ 16mA, 124 VAC @ 8 mA or 240VAC @8mA
- Class I, Division 1, Groups C, D; T4
- Tamb = -40°C to +70°C
- Model: 25972XP followed by 1, 2, 5 or 8;
- 24 VDC, 1.5 A, Class 2 Power Supply; 100% duty, 600#-in, 1.4 rpm
- Model 25972XP2 Control Circuit (Pulse Width Modulation): 24 VDC @ 16mA, or 124 VAC @ 8 mA
- Class I, Division 2, Groups B, C and D; T4
- Ex ec IIC T4 Gc
- Class I, Zone 2, AEx ec IIC T4 Gc
- IP54, Type 4X
- Ta = -40 °C to +50 °C
- Model: 25972XP followed by 3 or 4;
- CAN/CSA C22.2 No. 60079-0:19
- CAN/CSA C22.2 No. 60079-7:16
- CAN/CSA C22.2 No. 213-17
- UL 60079-0 7th ed.
- UL 60079-7: 5th ed.
- UL 121201 9th ed. (rev. April 1, 2021)
- CSA C22.2 No. 30:20
- C22.2 No. 14-18
- UL 508 – Edition 18
- UL 50 – Edition 13
- UL 50E – Edition 3
- UL 1203 – Edition 5
- Model: 25972XP* followed by 3 or 41, 2, 5 or 8 Class I, Division 2, Groups B, C and D T4:
- The actuator must not be opened, connected and/or disconnected or serviced unless the area is known to be non-hazardous.
- For the 25972XP2 model, the actuator must be grounded through the external grounding lug before connecting the Turck cables.
- Substitution of components may impair hazardous location suitability.
- All joints shall be properly tightened in order to maintain the declared ingress protection IP54 and the ingress protection required by Type 4X protection.
- 24VDC power must be supplied by a Class 2 power supply.
- All cover screws must be installed and tightened during normal operation. When cover removal is necessary for calibration, only do so when the area is known to be non-hazardous.
- General Note
- Project No.: LV-16096
- Listing Report No.: 11.03.16096-01
- Certificate No.: LC16096-1