Certification Record
LC1231890
Triangle Tube Phase III Co. Inc.
2024-05-31
New Jersey
United States
WH 299W, WH 399W, WH 470W, WH 499W
97.100.20, 27.060.01
- Instantaneous or Circulating Tank Water Heater
- Model Nos.: WH 299W, WH 399W, WH 470W, WH 499W
- Ratings:
Model (Heat Exchanger Type) 10+6 12+6 WH 399W WH 470W MIN MAX MIN MAX NG MBTU/HR 72 399 83 470 LP MBTU/HR 69 399 84 470 Fan Speed (RPM) 1550 6600 (NG) 6450 (LP)
1650 1750
7400 (NG) 7250 (LP)
Thermal Efficiency (%) per ANSI Z21.10.3-2015-CSA 4.3-2015 95.6 (NG) 95.8 (LP)
97.4 (NG) 95.4 (LP)
Model (Heat Exchanger Type) 8+4 12+6 WH 299W WH 499W MIN MAX MIN MAX NG MBTU/HR 46 299 83 500 LP MBTU/HR 46 299 84 500 Fan Speed (RPM) 1450 (NG) 1450 (LP)
6200 5950
1650 1750
8000 (NG) 7850 (LP)
Thermal Efficiency (%) per ANSI Z21.10.3-2015-CSA 4.3-2015 97.8 (NG) 97.6 (LP)
97.2 (NG) 95.2 (LP)
Electrical: 120 VAC, 60 Hz, less than 12 Amp
- ANSI Z21.10.3 – 2019 / CSA 4.3 – 209
- CSA 2.17- 2017
- Suitable for use with Natural Gas or Propane, for indoor use only.
- Not to be used with solid fuel.
- The ventilation of the boiler room must meet local and national standards and regulations, regardless of the selected supply of fresh air to the boiler.
- The flue gas system must be per the installation manual.
- Unit must be installed with a certified pressure relief valve supplied by the manufacturer as per instructions manual.
- Water pipes must be approved material for potable water.
General Note:
- LC Multiple Listing Certificate no.: LC16309-1ML-3
- Ties to the main applicant’s listing report no.: 50.00.16309-1_Rev.A