LC Clients

Certification Record

LC1231890
Triangle Tube Phase III Co. Inc.
2024-05-31
New Jersey
United States
WH 299W, WH 399W, WH 470W, WH 499W
97.100.20, 27.060.01
  • Instantaneous or Circulating Tank Water Heater
  • Model Nos.: WH 299W, WH 399W, WH 470W, WH 499W
  • Ratings:
    Model (Heat Exchanger Type) 10+6 12+6
      WH 399W WH 470W
    MIN MAX MIN MAX
    NG MBTU/HR 72 399 83 470
    LP MBTU/HR 69 399 84 470
    Fan Speed (RPM) 1550 6600 (NG)

    6450 (LP)

    1650

    1750

    7400 (NG)

    7250 (LP)

    Thermal Efficiency (%) per ANSI Z21.10.3-2015-CSA 4.3-2015 95.6 (NG)

    95.8 (LP)

    97.4 (NG)

    95.4 (LP)

    Model (Heat Exchanger Type) 8+4 12+6
    WH 299W WH 499W
    MIN MAX MIN MAX
    NG MBTU/HR 46 299 83 500
    LP MBTU/HR 46 299 84 500
    Fan Speed (RPM) 1450 (NG)

    1450 (LP)

    6200

    5950

    1650

    1750

    8000 (NG)

    7850 (LP)

    Thermal Efficiency (%) per ANSI Z21.10.3-2015-CSA 4.3-2015 97.8 (NG)

    97.6 (LP)

    97.2 (NG)

    95.2 (LP)

    Electrical:  120 VAC, 60 Hz, less than 12 Amp
  • ANSI Z21.10.3 – 2019 / CSA 4.3 – 209
  • CSA 2.17- 2017
  • Suitable for use with Natural Gas or Propane, for indoor use only.
  • Not to be used with solid fuel.
  • The ventilation of the boiler room must meet local and national standards and regulations, regardless of the selected supply of fresh air to the boiler.
  • The flue gas system must be per the installation manual.
  • Unit must be installed with a certified pressure relief valve supplied by the manufacturer as per instructions manual.
  • Water pipes must be approved material for potable water.

General Note:

  • LC Multiple Listing Certificate no.: LC16309-1ML-3
  • Ties to the main applicant’s listing report no.: 50.00.16309-1_Rev.A
Go to Top