Certification Record

LC1235009
Flodraulic Controls
2025-02-19
Ontario
Canada
MTR6813, MTR6313
29.240.30; 29.260.20; 29.260
  • Control Panel
  • Model No.: MTR6813
  • Ratings:
    • 460V, 3PH, 60A, 60Hz
    • Control Voltage 24VDC
    • Class I, Division 2, Group D; T3
  • Disconnect Switch
  • Model No.: MTR6313
  • Ratings:
    • 460V 3PH, 60A, 60Hz
    • Class I, Division 2, Group D; T3
    • Ta: -20°C to +50°C

Serial Nos.:

Panel Serial number Labtest Label Number
Control Panel 2024-00344 U-20708
Disconnect switch 2024-00343 U-20709
  • UL 508A 3rd Edition
  • UL 121201 9th Edition
  • UL 1203 5th Edition
  • Primary evaluation is based on report no: 11.03.22163-1. The only change to the newer model is the IS barrier Baluff, Sensor connected to this IS barrier, Model change in the explosion proof enclosure.
  • Control panel must not be installed in a hazardous location.
  • Installation manual to be provided to the customer by the manufacturer.
  • All the cable gland installed must be appropriate type as per the critical component list (Explosion proof)
  • Enclosure must be installed as per the requirements of installation instructions provided by the manufacturer.
  • All unused device openings must be fitted with a certified close-up plug.
  • The end user is to ensure appropriate earthing upon installation.
  • Power input and output (I/O) wiring shall be accordance with Class 1, Division 2 wiring method per the National Electrical Code (NFPA 70) for installation within U.S.
  • Final acceptance of this equipment when installed is subject to the jurisdiction of the local inspection authority.
  • Cables must be effectively clamped to prevent pulling or twisting.
  • The enclosure shall not be open when explosive atmosphere is present.
  • The RJ45 connector shall not be used when explosive atmosphere is present.

General Note:

  • Project no.: T-22392
  • LC Unit Verification Report no.: 11.03.22392-1_Rev.0
  • LC Unit Verification Certificate no.: LC22392-1