Certification Record
LC1231751
Victron Energy B.V.
2025-03-14
JG Almere
Netherlands
Stand-alone Inverter
- Stand-alone Inverter
- Model Nos.:
- Inverter 12 | 1200 120V VE.Direct NEMA GFCI
- Inverter 24 | 1200 120V VE.Direct NEMA GFCI
- Inverter 48 | 1200 120V VE.Direct NEMA GFCI
- Inverter 12 | 800 120V VE.Direct NEMA GFCI
- Inverter 24 | 800 120V VE.Direct NEMA GFCI
- Inverter 48 | 800 120V VE.Direct NEMA GFCI
- Inverter 12 | 500 120V VE.Direct NEMA GFCI
- Inverter 24 | 500 120V VE.Direct NEMA GFCI
- Inverter 48 | 500 120V VE.Direct NEMA GFCI
- Inverter 12 | 375 120V VE.Direct NEMA GFCI
- Inverter 24 | 375 120V VE.Direct NEMA GFCI
- Inverter 48 | 375 120V VE.Direct NEMA GFCI
- Inverter 12 | 250 120V VE.Direct NEMA GFCI
- Inverter 24 | 250 120V VE.Direct NEMA GFCI
- Inverter 48 | 250 120V VE.Direct NEMA GFCI
- Ratings:
Rating and main characteristics: 12/1200 24/1200 48/1200 Cont. Power at 25°C (nonlinear load, crest factor 3:1) 1200 VA Cont. Power at 25°C / 40°C 1000 / 900 W Peak power 2400 W Output AC voltage / frequency (adjustable) 100 – 128 VAC +/- 3% 50Hz or 60Hz +/- 0,1%
Output AC current 7 A 8 A 8 A Input voltage range, current 9,2–17 VDC 120A 18,4–34,0 VDC 60A
36,8–62,0 VDC 30A
Rating and main characteristics: 12/800 24/800 48/800 Cont. Power at 25°C (nonlinear load, crest factor 3:1) 800 VA Cont. Power at 25°C / 40°C 650 / 560 W Peak power 1500 W Output AC voltage / frequency (adjustable) 100 – 128 VAC +/- 3% 50Hz or 60Hz +/- 0,1%
Output AC current 5,4 A 5,4 A 5,4 A Input voltage range, current 9,2 – 17 VDC, 76A 18,4 – 34,0 VDC, 38A 36,8 – 62,0 VDC, 19A Rating and main characteristics: 12/500 24/500 48/500 Cont. Power at 25°C (nonlinear load, crest factor 3:1) 500 VA Cont. Power at 25°C / 40°C 400 / 350 W Peak power 900 W Output AC voltage / frequency (adjustable) 100 – 128 VAC +/- 3% 50Hz or 60Hz +/- 0,1%
Output AC current 3,35 A 3,35 A 3,35 A Input voltage range, current 9,2 – 17 VDC, 50A 18,4 – 34,0 VDC, 25A 36,8 – 62,0 VDC, 13A Rating and main characteristics: 12/375 24/375 48/375 Cont. Power at 25°C (nonlinear load, crest factor 3:1) 375 VA Cont. Power at 25°C / 40°C 300 / 260 W Peak power 700 W Output AC voltage / frequency (adjustable) 100 – 128 VAC +/- 3% 50Hz or 60Hz +/- 0,1%
Output AC current 2,5 A 2,5 A 2,5 A Input voltage range, current 9,2 – 17 VDC, 35A 18,4 – 34,0 VDC, 18A 36,8 – 62,0 VDC, 9A Rating and main characteristics: 12/250 24/250 48/250 Cont. Power at 25°C (nonlinear load, crest factor 3:1) 250 VA Cont. Power at 25°C / 40°C 200 / 175 W Peak power 400 W Output AC voltage / frequency (adjustable) 100 – 128 VAC +/- 3% 50Hz or 60Hz +/- 0,1%
Output AC current 1,7 A 1,7A 1,7 A Input voltage range, current 9,2 – 17 VDC, 23A 18,4 – 34,0 VDC, 12A 36,8 – 62,0 VDC, 6A
- UL 458 (Ed.6)
- Inverter intended to be used indoors, built-in in a cabinet, non-condensing humidity of max 95%, in ambient temperature of -40 to +60°C.
General Note:
- Project no.: 20760A
- LC Listing Report no.: 10.00.20760-1_Rev.A
- LC Certificate no.: LC20760-1