LC Clients

Certification Record

LC1234957
Northridge Electric Inc.
2025-10-03
Ontario
Canada
14438A, 14438B
21.180, 29.260.20
  • Explosion Proof Starter Panel
  • Model Number: 14438A,14438B
  • Ratings
    • 230 Vac, 3 Phase, 15 Amps, 60Hz
    • Class I, Division 1, Group D, T3
    • -40°C to +35°C

Serial Nos.:

Panel Serial Number Labtest Label number
NOR-14438A C-20171
NOR-14438B C-20172
  • CSA C22.2 No. 30:20
  • CSA C22.2 No. 286:17*

*Compliance was accepted from the QPS evaluation report number LPS124-1

  • All unused device openings must be fitted with a certified close-up plug.
  • All cable glands used in the device must be of certified Class I, Division 1 cable glands.
  • The end user is to ensure appropriate earthing upon installation.
  • Power input and output (I/O) wiring shall be accordance with Class 1, Division 1 wiring method per the Canadian Electrical Code for installation within Canada.
  • Final acceptance of this equipment when installed is subject to the jurisdiction of the local inspection authority.
  • Cables must be effectively clamped to prevent pulling or twisting.
  • Customers will be responsible for maintaining the temperature inside the explosion proof chamber above -20°C.
  • The enclosure shall not be open when the explosive atmosphere is present.

General Note:

  • Project no.: 25-1319
  • LC Unit Verification Report no.: 11.03.25.1319-1_Rev.0
  • LC Unit Verification Certificate no.: LC25-1319-1
Go to Top