LC Clients

Certification Record

LC1229903
CE2K S.r.l.
2025-12-19
Lecco
Italy
EJBS (Stainless Steel) Series Enclosures without windows EJBS-A, EJBS-B, EJBS-C, EJBS-D, EJBS-E, EJBS-F, EJBS-G & EJBS-H EJBA (Aluminum) Series Enclosures without windows. EJB-A, EJB-B, EJB-C, EJB-D, EJB-E, EJB-F, EJB-G and EJB-H.
21.180
  •  Empty ENCLOSURES (SS and AL)
  •  Model Nos.:
    1. EJBS (Stainless Steel) Series Enclosures without windows
      EJBS-A, EJBS-B, EJBS-C, EJBS-D, EJBS-E, EJBS-F, EJBS-G & EJBS-H
    2. EJBA (Aluminum) Series Enclosures without windows.
      EJB-A, EJB-B, EJB-C, EJB-D, EJB-E, EJB-F, EJB-G and EJB-H.
  • Rating:
    • Ex db IIB+H2 T6/T5/T4 Gb
    • Class I Zone 1 AEx db IIB+H2 T6/T5/T4 Gb
    • Ex tb IIIC T85°C / T100°C / T135°C Db IP66/IP67
    • Class II Zone 21 AEx tb IIIC T85°C/T100°C/T135C Db
    • Ambient Temperature: -50°C to +60°C
    • Zone 1 and Zone 21
 

TYPES OF ENCLOSURES

 

TEMPERATURE CLASS

 

MAXIMUM POWER DISSIPATED

(for SS and AL Enclosures)

GAS DUST 40°C 50°C 60°C
 

 

EJB-A

T6 T85°C 90W 60W 25W
T5 T100°C 120W 95W 75W
T4 T135°C 205W 180W 155W
 

 

EJB-B

T6 T85°C 125W 90W 55W
T5 T100°C 180W 145W 110W
T4 T135°C 305W 270W 235W
 

 

EJB-C

T6 T85°C 210W 150W 95W
T5 T100°C 295W 235W 180W
T4 T135°C 500W 440W 380W
 

 

EJB-D

T6 T85°C 255W 185W 115W
T5 T100°C 360W 290W 220W
T4 T135°C 610W 535W 465W
 

 

EJB-E

T6 T85°C 265W 200W 125W
T5 T100°C 390W 315W 240W
T4 T135°C 655W 580W 505W
 

 

EJB-F

T6 T85°C 350W 265W 165W
T5 T100°C 515W 415W 315W
T4 T135°C 850W 755W 660W
 

 

EJB-G

T6 T85°C 410W 315W 195W
T5 T100°C 610W 495W 375W
T4 T135°C 1020W 905W 790W
 

 

EJB-H

T6 T85°C 510W 390W 245W
T5 T100°C 610W 460W 320W
T4 T135°C 1260W 1120W 975W
  • CSA C22.2 No. 60079-0:19
  • CSA C22.2 No. 60079-1:16
  • CSA C22.2 No. 60079-31:15
  • UL 60079-0, Ed. 7
  • UL 60079-1, Ed. 7
  • UL 60079-31, Ed. 2
  • This certification is for empty Stainless steel/ Aluminum enclosures only.
  • The content of the Ex-component enclosure equipment may be placed in any arrangement, provided that, for group IIB and IIB+H2 an area of at least 40% of each cross-sectional area remains free.
  • The accessories used for cable entries and for closing unused openings shall be certified according to UL 60079-0 and CSA C22.2 No. 60079-0, UL 60079-1, CSA C22.2 No 60079-1 and, UL 60079-31 and CSA C22.2 No 60079-31. A minimum degree of protection IP66 (with operators installed) and IP67 (without operators installed) shall be guaranteed according to CSA C22.2 No. 60529: 2016 (R2021) standard.

Specific Conditions of Use:

  • THIS EQUIPMENT SHALL BE INSTALLED SO THAT THE FLANGED JOINT(S) ARE NOT WITHIN (40 mm) OF A SOLID OBJECT THAT IS NOT PART OF THIS EQUIPMENT. i.e. THE MINIMUM DISTANCE BETWEEN FLAMEPROOF FLANGED JOINT OF THE ENCLOSURE AND EXTERNAL OBSTACLE SHOULD BE 40 mm FOR IIB+H2 EXECUTION.
  • SEAL SHALL BE PROVIDED WITHIN 50 mm OF THE THREADED CONDUIT.
  • THE COVER FIXING SCREWS IF REPLACED, SHOULD BE OF SAME TYPE OR BETTER QUALITY IN TERMS OF TENSILE STRENTH AND YIELD STRESS i.e. Use screws of quality (A4-70) with tensile strength of at least 700 N/mm

General Notes:

  • Project No.: LV-15427B
  • LC Certificate No.: LC25CA15427-1
  • LC Listing Report No.: 11.00.15427-1_RevB
Go to Top