LC Clients

Certification Record

LC1234957
Northridge Electric Inc.
2025-12-29
Ontario
Canada
14438C,14438D,14438-1,14438-2,14438-3, 14438-4,14438-5,14438-6,14438-7
21.180, 29.260.20
  • Explosion Proof Starter Panels
  • Model Number:
    • 14438C,14438D,14438-1,14438-2,14438-3,
      14438-4,14438-5,14438-6,14438-7
  • Ratings
    • 230Vac, 3 Phase, 15 Amps, 60Hz
    • Class I, Division 1, Group D, T3
    • -40°C to +35°C

Serial No.s:

Panel Serial Number Labtest Label Number
NOR-14438C C-20175
NOR-14438D C-20176
NOR-14438-1 C-20177
NOR-14438-2 C-20178
NOR-14438-3 C-20179
NOR-14438-4 C-20180
NOR-14438-5 C-20181
NOR-14438-6 C-20182
NOR-14438-7 C-20183
  • CSA C22.2 No. 30:20
  • CSA C22.2 No. 286:17
  • All unused device openings must be fitted with a Class I, Division 1 certified close-up plug.
  • All cable glands used in the device must be of certified Class I, Division 1 cable glands.
  • The end user is to ensure appropriate earthing upon installation.
  • Power input and output (I/O) wiring shall be accordance with Class I, Division 1 wiring method per the Canadian Electrical Code for installation within Canada.
  • Final acceptance of this equipment when installed is subject to the jurisdiction of the local inspection authority.
  • Cables must be effectively clamped to prevent pulling or twisting.
  • Customers will be responsible for maintaining the temperature inside the explosion proof chamber above -20°C.
  • The enclosure shall not be open when the explosive atmosphere is present.

General Note:

  • Project no.: 25-5665
  • LC Unit Verification Report no.: 11.03.25-1319-1_Rev 0
  • LC Unit Verification Certificate no.: LC25-5665-1
Go to Top