Certification Record
LC1234957
Northridge Electric Inc.
2025-12-29
Ontario
Canada
14438C,14438D,14438-1,14438-2,14438-3, 14438-4,14438-5,14438-6,14438-7
21.180, 29.260.20
- Explosion Proof Starter Panels
- Model Number:
- 14438C,14438D,14438-1,14438-2,14438-3,
14438-4,14438-5,14438-6,14438-7
- 14438C,14438D,14438-1,14438-2,14438-3,
- Ratings
- 230Vac, 3 Phase, 15 Amps, 60Hz
- Class I, Division 1, Group D, T3
- -40°C to +35°C
Serial No.s:
| Panel Serial Number | Labtest Label Number |
| NOR-14438C | C-20175 |
| NOR-14438D | C-20176 |
| NOR-14438-1 | C-20177 |
| NOR-14438-2 | C-20178 |
| NOR-14438-3 | C-20179 |
| NOR-14438-4 | C-20180 |
| NOR-14438-5 | C-20181 |
| NOR-14438-6 | C-20182 |
| NOR-14438-7 | C-20183 |
- CSA C22.2 No. 30:20
- CSA C22.2 No. 286:17
- All unused device openings must be fitted with a Class I, Division 1 certified close-up plug.
- All cable glands used in the device must be of certified Class I, Division 1 cable glands.
- The end user is to ensure appropriate earthing upon installation.
- Power input and output (I/O) wiring shall be accordance with Class I, Division 1 wiring method per the Canadian Electrical Code for installation within Canada.
- Final acceptance of this equipment when installed is subject to the jurisdiction of the local inspection authority.
- Cables must be effectively clamped to prevent pulling or twisting.
- Customers will be responsible for maintaining the temperature inside the explosion proof chamber above -20°C.
- The enclosure shall not be open when the explosive atmosphere is present.
General Note:
- Project no.: 25-5665
- LC Unit Verification Report no.: 11.03.25-1319-1_Rev 0
- LC Unit Verification Certificate no.: LC25-5665-1