Certification Record
LC1229712
The Group Simoneau Inc.
2025-12-17
Quebec
Canada
Maverick M-500 W
91.140.40, 97.100.20
- Hot Water Boilers
- Model No: Maverick M-500 W
- Ratings:
- Input Rate: 20.290.000 BTU/hr – Natural Gas
- Electrical Rating:
- 575 Vac, 36.5 Amp – motor circuit
- 120 Vac, 5 Amp – control circuit
Serial No.:
| Unit Serial No. | LC labels Serial No |
| 5515 | C-20062 |
| 5514 | C-20063 |
| 5516 | C-20064 |
- CSA B149.3 – 2025
- All the units are approved for use with Natural Gas only and they are identical in construction and have the same components.
- The units approval is valid only for Oakridge Centre, 650 W 41St Avenue, Vancouver, BC, V5Z 2M9, Canada location.
- The units have an intermittent pilot ignited with spark ignition.
- The units have a start ignition point at 40% of declared input.
- Pre-purge time 74 seconds
- Post purge time 30 seconds.
- The thermostat can be set at maximum 203°F with normal temperature use pre-set at 176°F.
- The trial for ignition is 6 seconds. The ignitor starts 2 seconds before the gas is open to the pilot and it has 1 tryout before the unit goes in lock down.
- The flame failure was measured at 1.5 seconds.
- The units are vented in an exhaust line provided with automatic damper that is part of the building automation.
- The units are provided with Low water cut-off sensor and relief valves installed on the hot water line, close to the ASME stamped tank.
- Each unit is provided with the following safety components:
- 2 Hi-limit temperature sensors set at 200°F and 250°F
- Certified Burner System containing power burner, burner head, ignition module, provided with flame sensor and air flow pressure switch.
- Primary temperature control pre-set to maximum 176°F
- Pressure sensors for proving the combustion fan and the damper prior initiation of ignition.
General Note:
- Project no.: 25-5723
- LC Unit Verification Report no.: 50.00.25-5723-1_Rev.0