Certification Record
LC1231751
Victron Energy B.V.
2026-04-14
JG Almere Haven
Netherlands
Stand-along Inverter 12, 24, 48
29.200
- Stand-alone Inverter
- Model Nos.:
- Inverter 12 | 1600 120V VE.Direct NEMA GFCI
- Inverter 24 | 1600 120V VE.Direct NEMA GFCI
- Inverter 48 | 1600 120V VE.Direct NEMA GFCI
- Inverter 12 | 1200 120V VE.Direct NEMA GFCI
- Inverter 24 | 1200 120V VE.Direct NEMA GFCI
- Inverter 48 | 1200 120V VE.Direct NEMA GFCI
- Inverter 12 | 800 120V VE.Direct NEMA GFCI
- Inverter 24 | 800 120V VE.Direct NEMA GFCI
- Inverter 48 | 800 120V VE.Direct NEMA GFCI
- Inverter 12 | 500 120V VE.Direct NEMA GFCI
- Inverter 24 | 500 120V VE.Direct NEMA GFCI
- Inverter 48 | 500 120V VE.Direct NEMA GFCI
- Inverter 12 | 375 120V VE.Direct NEMA GFCI
- Inverter 24 | 375 120V VE.Direct NEMA GFCI
- Inverter 48 | 375 120V VE.Direct NEMA GFCI
- Inverter 12 | 250 120V VE.Direct NEMA GFCI
- Inverter 24 | 250 120V VE.Direct NEMA GFCI
- Inverter 48 | 250 120V VE.Direct NEMA GFCI
- Ratings:
Inverter VE.Direct 120V 12/250
24/25048/25012/375 24/375
48/375
12/500
24/50048/50012/800
24/800
48/80012/1200 24/1200
48/120012/1600
24/1600
48/1600Cont. Power at 25°C 250W 375W 500W 800W 1200W 1500W Cont. Power at 40°C 200W 300W 438W 650W 1100W 1350W Time-limited power (cold start) 300W/15s 450W/25s 500W/1h 900W/1h 1300W/1h 1700W/1h Peak power 400W/2s 600W/2s 750W/2s 1200W/15s 1600W/15s 2100W/15s Output AC (voltage, current, Frequency)
1.70Aac 2.5Aac 3.35Aac 5.4Aac 8.0Aac 10.9Aac 120Vac +/-3% 60Hz +/-0.1%
Input DC voltage range
current:
12V battery
24V battery
48V battery
9.2 – 17V 18.4 – 34.0V
36.8 – 62V
23Adc 12Adc
6Adc
35Adc 18Adc
9Adc
50Adc 25Adc
13Adc
76Adc 38Adc
19Adc
120Adc 60Adc
30Adc
160Adc 80Adc
40Adc
Operating temperature range -40 to +60°C (fan-assisted cooling) Power derating 1.25% per °C above 40°C
- UL 458 (Ed.6)
- Inverter intended to be used indoors, built-in in a cabinet, non-condensing humidity of max 95%, in ambient temperature of -40 to +60°C.
- This is a Safety class I product (supplied with a protective grounding terminal). The chassis must be grounded.
- The AC output is isolated from the DC input and the chassis unless the unit is equipped with a Ground Fault Circuit Interruper (GFCI). Local regulations may require a true neutral. In this case, one of the AC output wires must be connected to the chassis, and the chassis must be connected to a reliable ground. The true neutral is needed to ensure the current operation of an earth leakage circuit breaker.
General Note:
- Project no.: 20760B
- LC Listing Report no.: 10.00.20760-1_Rev.B
- LC Certificate no.: LC20760-1