Certification Record
LC1235009
Flodraulic Controls
2026-05-26
Ontario
Canada
MTR6813
- Control Panel
- Model No.: MTR6813
- Ratings:
- 460V, 3PH, 60A, 60Hz
- Control Voltage 24VDC
- Class I, Division 2, Group D; T3
- Disconnect Switch
- Model No.: MTR6313
- Ratings:
- 460V 3PH, 60A, 60Hz
- Class I, Division 1, Group D; T3
- Ta: -20°C to +50°C
Serial No.:
| Unit Serial | Serial number | Labtest Label Number |
| Disconnect Switch | 2024-00343 | U-20911 |
- UL 508A 3rd Edition
- UL 121201 9th Edition
- UL 1203 5th Edition
- Control Panel and Disconnect Switch can be installed in a hazardous location according to their HazLoc ratings.
- The ½ inch NPT plug must be fully engaged with min. 5 threads
- Installation manual to be provided to the customer by the manufacturer.
- All the cable gland installed must be appropriate as per the critical component list (Explosion proof).
- Enclosure must be installed as per the requirements of installation instructions provided by the manufacturer.
- All unused device openings must be fitted with a certified close-up plug.
- The end user is to ensure appropriate earthing upon installation.
- Power input and output (I/O) wiring shall be accordance with Class I, Division 2 wiring method per the National Electrical Code (NFPA 70) for installation within U.S.
- Final acceptance of this equipment when installed is subject to the jurisdiction of the local inspection authority.
- Cables must be effectively clamped to prevent pulling or twisting.
- The enclosure shall not be open when explosive atmosphere is present.
- The RJ45 connector should not be used when explosive atmosphere is present.
General Note:
- Project no.: 25-1403
- LC Unit Verification Report no.: 11.03.25-1403-1_Rev.0
- LC Unit Verification Certificate no.: LC25-1403-1