Certification Record

LC1235009
Flodraulic Controls
2026-05-26
Ontario
Canada
MTR6813
  • Control Panel
  • Model No.: MTR6813
  • Ratings:
    • 460V, 3PH, 60A, 60Hz
    • Control Voltage 24VDC
    • Class I, Division 2, Group D; T3
  • Disconnect Switch
  • Model No.: MTR6313
  • Ratings:
    • 460V 3PH, 60A, 60Hz
    • Class I, Division 1, Group D; T3
    • Ta: -20°C to +50°C

Serial No.:

Unit Serial Serial number Labtest Label Number
Disconnect Switch 2024-00343 U-20911
  • UL 508A 3rd Edition
  • UL 121201 9th Edition
  • UL 1203 5th Edition
  • Control Panel and Disconnect Switch can be installed in a hazardous location according to their HazLoc ratings.
  • The ½ inch NPT plug must be fully engaged with min. 5 threads
  • Installation manual to be provided to the customer by the manufacturer.
  • All the cable gland installed must be appropriate as per the critical component list (Explosion proof).
  • Enclosure must be installed as per the requirements of installation instructions provided by the manufacturer.
  • All unused device openings must be fitted with a certified close-up plug.
  • The end user is to ensure appropriate earthing upon installation.
  • Power input and output (I/O) wiring shall be accordance with Class I, Division 2 wiring method per the National Electrical Code (NFPA 70) for installation within U.S.
  • Final acceptance of this equipment when installed is subject to the jurisdiction of the local inspection authority.
  • Cables must be effectively clamped to prevent pulling or twisting.
  • The enclosure shall not be open when explosive atmosphere is present.
  • The RJ45 connector should not be used when explosive atmosphere is present.

General Note:

  • Project no.: 25-1403
  • LC Unit Verification Report no.: 11.03.25-1403-1_Rev.0
  • LC Unit Verification Certificate no.: LC25-1403-1