Certification Record

LC1250104
Ezilon Building Solutions Ltd.
2026-07-14
British Columbia
Canada
CS145 Series Composite Window (C + FW) , CS145 Casement Window , CS145 Fixed Window , Vertical Mullion Assembly
91.060.50
  • CS145 Series Composite Window (C + FW)
    • Class CW – PG70 – Size tested: 2400 x 2100 mm (~94.5 x 82.7 in)
    • Positive/ Negative ASD Design Pressure (DP) = 3360 Pa
    • Water Penetration Resistance Test Pressure = 510 Pa
    • Canadian Air Infiltration/ Exfiltration = A3 Level
  • CS145 Casement Window
    • Model No.: EZ-CS145-C-IGXX
    • Class CW – PG70 – Size tested: 810 x 1997 mm (~31.9 x 78.6 in) – Type C
    • Positive/ Negative ASD Design Pressure (DP) = 3360 Pa
    • Water Penetration Resistance Test Pressure = 510 Pa
    • Canadian Air Infiltration/ Exfiltration = A3 Level
  • CS145 Fixed Window
    • Model No: EZ-CS145-FW-IGXX
    • Class CW – PG70 – Size tested: 1590 x 2100 mm (~62.6 x 82.7 in) – Type FW
    • Positive/ Negative ASD Design Pressure (DP) = 3360 Pa
    • Water Penetration Resistance Test Pressure = 510 Pa
    • Canadian Air Infiltration/ Exfiltration = Fixed Level
  • Vertical Mullion Assembly
    • Class CW – PG70 – Size tested: 2070 mm (81.5 in) span/ 1200 mm (47.2 in) TribWd MA

Thermal simulation performed for 3 glazing options.
Legend for Coding System and Energy Performance Values:

  • XX’ is the applicable glazing option (3 options currently as shown below)

Glazing Options:

  • Casement Window
    • Option 01: H-CLR-PTE75A-6 on 6mm Clear / 15mm Argon (95%) / H-CLR-PTE75A-6 on 6mm Clear / 0.3mm Vacuum / J-CLR-JN91-6 on 6mm Clear
    • Option 02: H-CLR-PTE75A-6 on 6mm Clear / 0.3mm Vacuum / XDTN0180-T on 6mm Clear / 15mm Argon (95%) / H-CLR-PTE75A-6 on 6mm Clear / 0.3mm Vacuum / XDTN0180-T on 6mm Clear
    • Option 03: H-CLR-PTE75A-6 on 6mm Clear / 16mm Argon (90%) / J-CLR-PDE80A-6 on 6mm Clear / 16mm Argon (90%) / J-CLR-JN91-6 on 6mm Clear
  • Fixed Window
    • Option 01: H-CLR-PTE75A-6 on 6mm Clear / 15mm Argon (95%) / H-CLR-PTE75A-6 on 6mm Clear / 0.3mm Vacuum / J-CLR-JN91-6 on 6mm Clear
    • Option 02: H-CLR-PTE75A-6 on 6mm Clear / 0.3mm Vacuum / XDTN0180-T on 6mm Clear / 15mm Argon (95%) / H-CLR-PTE75A-6 on 6mm Clear / 0.3mm Vacuum / XDTN0180-T on 6mm Clear
    • Option 03: H-CLR-PTE75A-6 on 6mm Clear / 16mm Argon (95%) / J-CLR-PDE80A-6 on 6mm Clear / 16mm Argon (95%) / J-CLR-JN91-6 on 6mm Clear

Thermal Simulation Results:

  • CS145 Casement Window
    • IG01: U factor (W/m2-K): 1.28; Solar Heat Gain Coefficient: 0.11; Visible Transmittance: 0.23; Air Leakage: 0.3; Energy Rating: 18.
    • IG02: U factor (W/m2-K): 1.13; Solar Heat Gain Coefficient: 0.10; Visible Transmittance: 0.16; Air Leakage: 0.3; Energy Rating: 20.
    • IG03: U factor (W/m2-K): 1.28; Solar Heat Gain Coefficient: 0.13; Visible Transmittance: 0.24; Air Leakage: 0.3; Energy Rating: 19.
  • CS145 Fixed Window
    • IG01: U factor (W/m2-K): 0.81; Solar Heat Gain Coefficient: 0.19; Visible Transmittance: 0.42; Air Leakage: 0.1; Energy Rating: 33.
    • IG02: U factor (W/m2-K): 0.62; Solar Heat Gain Coefficient: 0.17; Visible Transmittance: 0.28; Air Leakage: 0.1; Energy Rating: 36.
    • IG03: U factor (W/m2-K): 0.93; Solar Heat Gain Coefficient: 0.21; Visible Transmittance: 0.44; Air Leakage: 0.1; Energy Rating: 32.
  • AAMA/WDMA/CSA 101/I.S.2/A440-17
  • CSA A440S1:19
  • CSA A440.2:19
  • Products are certified for Canadian Market only.

General Notes:

  • LC Project no.: 25-1274
  • LC Certificate no.: LC25-1274-2
  • LC Listing Report no.: 40.00.25-1274-2_Rev 0