LC Clients

Certification Record

LC1234178
McCue Engineering Contractors
2026-07-31
British Columbia
Canada
046-0005 – WWTP
29.260.20 , 29.260 , 29.240.30 , 25.040.40
  • Screen Container (Container – C1) of 20ft Containerized Wastewater Treatment Plant
  • Model No:
    • 046-0005 – WWTP
  • Ratings:
    • Input Power:
      • 600 VAC, 800 AAC, 3 Ph, 60 Hz
    • Hazardous Location:
      • Class I, Division 2, Group C, D, T3C
        ▪ x2 – 600 VAC , 2.65 A, 2 HP
        ▪ x2 – 600 VAC , 0.75 A, 0.5 HP
        ▪ x1 – 600 VAC , 14 A, 10 kW
        ▪ x4 – 120 VAC , 15 A
      • Ta: +5°C to +27°C
Equipment Serial Number LabTest Certification Label
Screen Container C-20054
  • CSA C22.2 No. 14:18 (R2022)
  • CSA C22.2 No. 213: 2017 (R2022)
  • The final installation of the device shall meet the requirements of CEC for wiring method in Zone 2 and Division 2 and is subjected to acceptance of local authorities having jurisdiction.
  • End users shall follow specific installation and operating instructions supplied by the manufacturer to prevent exceeding the heat dissipating limits for the desired temperature code for an operating ambient.
  • The container metal frame must be connected to ground upon installation.
  • No changes to or modifications of the devices or components are permitted without additional assessment.

General Note:

  • LC Project no.: 26-5884
  • LC Unit Verification Certificate no.:LC26-5884-1
  • LC Unit Verification Report no.: 11.00.26-5884-1_Rev 0
Go to Top