Certification Record
LC21800
RIC Electronics Ltd.
2026-08-11
British Columbia
Canada
SB7 Series
29.200
- Standby Battery Charger
- Model Nos.: SB7 Series (see table below)
- Ratings: 30Amp Integrated & 200Amp Integrated Assembly (see the table on the next page)
| MODEL | CHARGER OUTPUT (NOM) | INPUT CURRENT,
1PH, XX = ‘AB’ |
INPUT CURRENT, 1PH, XX = ‘DE’ | INPUT CURRENT,
3PH, XX = ‘F’ |
INPUT CURRENT, 3PH, XX = ‘GH’ | ENC. SIZE CODE | |||||||
| SB7 P/N | DC VOLTS | DC AMPS | 120 Vac | 208 Vac | 240 Vac | 480 Vac | 600 Vac | 208 Vac | 230 Vac | 240 Vac | 480 Vac | 600 Vac | SEE BELOW |
| SB7-24/5-XX-1 | 24 | 5 | 2.0 | 1.2 | 1.0 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | A |
| SB7-24/10-XX-1 | 24 | 10 | 3.9 | 2.3 | 2.0 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | A |
| SB7-24/20-XX-1 | 24 | 20 | 7.9 | 4.5 | 3.9 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | A |
| SB7-24/30-XX-1 | 24 | 30 | 11.8 | 6.8 | 5.9 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | A |
| SB7-48/5-XX-1 | 48 | 5 | 3.7 | 2.1 | 1.9 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | A |
| SB7-48/10-XX-1 | 48 | 10 | 7.4 | 4.3 | 3.7 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | A |
| SB7-48/20-XX-1 | 48 | 20 | 14.9 | 8.6 | 7.4 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | A |
| SB7-48/30-XX-1 | 48 | 30 | 22.3 | 12.9 | 11.1 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | A |
| SB7-125/5-XX-1 | 125 | 5 | 9.0 | 5.2 | 4.5 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | A |
| SB7-125/10-XX-1 | 125 | 10 | 18.1 | 10.4 | 9.0 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | A |
| SB7-125/20-XX-1 | 125 | 20 | 36.1 | 20.8 | 18.0 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | A |
| SB7-1250/30-XX-1 | 125 | 30 | 54.2 | 31.3 | 27.1 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | A |
| SB7-250/10-XX-1 | 250 | 10 | 36.1 | 20.8 | 18.0 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | A |
| SB7-24/100-XX-1 | 24 | 100 | 39.3 | 22.7 | 19.6 | 9.8 | 8.1 | 11.2 | 10.1 | 9.7 | 4.8 | 3.9 | O |
| SB7-24/125-XX-1 | 24 | 125 | 49.1 | 28.3 | 24.5 | 12.2 | 10.1 | 14.0 | 12.6 | 12.1 | 6.0 | 4.8 | O |
| SB7-24/150-XX-1 | 24 | 150 | 59.0 | 34.0 | 29.4 | 14.7 | 12.1 | 16.8 | 15.2 | 14.6 | 7.2 | 5.8 | O |
| SB7-24/200-XX-1 | 24 | 200 | 78.6 | 45.4 | 39.3 | 19.6 | 16.1 | 22.3 | 20.2 | 19.4 | 9.6 | 7.8 | O |
| SB7-48/100-XX-1 | 48 | 100 | 74.0 | 42.9 | 37.1 | 18.5 | 15.2 | 20.6 | 18.6 | 17.9 | 8.9 | 7.2 | O |
| SB7-48/125-XX-1 | 48 | 125 | 93.0 | 53.6 | 46.4 | 23.2 | 19.0 | 25.8 | 23.3 | 22.4 | 11.1 | 9.0 | O |
| SB7-48/150-XX-1 | 48 | 150 | 112.0 | 64.4 | 56.0 | 27.8 | 22.9 | 30.9 | 28.0 | 26.9 | 13.3 | 10.7 | O |
| SB7-48/200-XX-1 | 48 | 200 | 149.0 | 85.0 | 74.0 | 37.1 | 30.5 | 41.2 | 37.3 | 35.9 | 17.8 | 14.3 | O |
| SB7-125/100-XX-1 | 125 | 100 | 180.0 | 104.0 | 90.0 | 45.0 | 37.0 | 52.4 | 47.4 | 45.6 | 22.6 | 18.2 | O |
| SB7-125/125-XX-1 | 125 | 125 | 225.0 | 130.0 | 112.5 | 56.3 | 46.3 | 65.5 | 59.3 | 57.0 | 28.3 | 22.8 | O |
| SB7-125/150-XX-1 | 125 | 150 | 270.0 | 156.0 | 135.0 | 67.5 | 55.5 | 78.6 | 71.1 | 68.4 | 33.9 | 27.3 | O |
| SB7-125/200-XX-1 | 125 | 200 | 360.0 | 208.0 | 180.0 | 90.0 | 74.0 | 104.8 | 94.8 | 91.2 | 45.2 | 36.4 | O |
| SB7-250/100-XX-1 | 250 | 100 | 180.0 | 104.0 | 90.0 | 45.0 | 37.0 | 52.4 | 47.4 | 45.6 | 22.6 | 18.2 | O |
| ENCLOSURE CODES | MODEL | DIMENSIONS | MANUFACTURER |
| A | EN4SD242016 | 61x50x40cm | HAMMOND |
| O | RIC703124 | 180x80x61cm | RIC |
- CSA C22.2 No. 107. 1-16
- CSA C22.2 No. 107.2-01 (2016)
- UL 1012 Edition 8
- Unit shall be marked as with the marking noted in the Marking section.
- The units are permanently connected Overvoltage Category II, indoor use only in Pollution Degree II environment at a maximum ambient of 40 °C
- The following is not the intended use of the units as per CSA-C22.2 No. 107.1-16:
- Industrial DC PCE (Power Conversion Equipment)
- PCE for use in recreational vehicles
- Transfer Switches
- Inverters
- Telecommunication Equipment PCE
- Cable TV PCE
- PCE for use in photovoltaic (PV) systems
- Interactive inverters and PCE
- DC charge controllers
- Electric vehicle chargers
- PV modules with integrated power conversion equipment (PVIPCE)
- Inverters for use in vehicles
- PCE for use in marine applications
- PCE not intended to be installed in parallel or series with each other.
- The following is not the intended use of the units as per CSA-C22.2 No. 107.2-01:
-
Chargers Intended to be Used for Special Applications
-
Marine Battery Chargers
-
Transformerless Non-isolated Battery Chargers for Special-Purpose Battery Packs
-
- The following is not the intended use of the units as per UL 1012:
-
Outdoor-Use Power Units
-
Plug-In Power Units
-
School-Laboratory Power Supplies
-
Power Supplies Rated More Than 10-Kilovolt-Amperes
-
Class 3 Outputs – DC, or AC Derived from Non-Linear Sources
-
Foreign Voltage Adapters
- Rechargeable Batteries With Integral Chargers
-
Power Units for Installation in Air-handling Spaces
-
General Note:
- LC Project no.: 16334A
- LC Certificate no.: LC16334-1
- LC Listing Report no.: 10.00.16334-1_Rev A