LC1253096
Caron Measurement and Controls Ltd.
2026-09-15
Alberta
Canada
CMC-ELM-TMR-00-XX, CMC-ELM-TMR-MD-XX, CMC-ELM-TMR-AC1D, CMC- ELM-MSXP
33.160.01; 35.020
  • Eliminator Programmable Controllers (Explosion Proof) Series
  • Model Nos.: CMC-ELM-TMR-00-XX, CMC-ELM-TMR-MD-XX, CMC-ELM-TMR-AC1D, CMC-
    ELM-MSXP
  • Ratings:
    • Class I, Division 1, Group D T4A;
    • Class I, Zone 1 Ex db IIA, IIB T4A/T5 Gb;
    • Hazardous locations in an ambient temperature range of -40°C to +40°C.
    • Type 4X.
  1. With Motor Control Board (CMC-ELM-TMR-AC-1D, CMC-ELM-TMR-MD-XX, CMC-ELM-000-MDXX) – Round Enclosures, (CMC-ELM-TMR-AC-1D includes square enclosure and does not necessarily require -40°C)
    • Hazardous Location Ratings:
      1. Class I, Division 1, Group D T4A; Class I, Zone 1 Ex db IIA, IIB T4A Gb;
      2. Type 4X
      3. Ambient Temperature: -40°C ≤ Tamb ≤ 40°C
    • Electrical Ratings: Voltage: 10-30 VDC, Max Cont. Current: 20A.
  2.  2. Without Motor Control Board (CMC-ELM-TMR-00-XX, CMC-ELM-MSXP, CMC-ELM-MSXPW)
    • Hazardous Location Ratings:
      1. Class I, Division 1, Group C, D T5; Class I, Zone 1 Ex db IIA, IIB T5 Gb;
      2. Type 4X
      3. Ambient Temperature: -40°C ≤ Tamb ≤ 40°C
    • Electrical Ratings: Voltage: 9-30 VDC, Max Cont. Current: 2A
  1. 3. CMC-ELM-MSXPW
    • Hazardous Ratings:
      1. Class I, Division 1, Group C, D T5; Class I, Zone 1 Ex db IIA, IIB T5 Gb;
      2. Type 4X
      3. Ambient Temperature: -40°C ≤ Tamb ≤ 40°C
    • Electrical Ratings: Voltage: 6-30 VDC, Max Cont. Current: 2A

 

  • CSA C22.2 No. 14-18 (R2022) – Industrial Control Equipment
  • UL 508, Edition 18 – Industrial Control Equipment
  • CSA C22.2 No. 30:20 – Explosion Proof Equipment
  • CSA C22.2 No. 60079-0:2019 – Explosive atmospheres – Part 0: Equipment – General requirements
  • CSA-C22.2 No. 60079-1:16 (R2021) – Explosive atmospheres – Part 1: Equipment protection by flameproof enclosures “d”
  • UL 1203 – Edition 5 – Explosion Proof and Dust-Ignition Proof Electrical Equipment for use in Hazardous (Classified) Locations
  • UL60079-0 – Edition 7 – Standard for Explosive atmospheres – Part 0: Equipment – General Requirements.
  • UL 60079-1 – Edition 7 – Standard for Explosive Atmospheres – Part 1: Equipment Protection by Flameproof Enclosures.
  1. The approved construction of the labelled product is as described below in this report.
  2. Certification is voided if the labeled product has been modified or changed by the manufacturer or end user after labeling.
  3. Certification covers only safety from electric shock and fire/explosion hazards and apply only to the construction elements described in this report.
  4. LC did not evaluate the suitability of the use of equipment involving toxic or corrosive gases; steam locations defined as hazardous locations by the Canadian Electrical Code or the National Electrical Code.

General Note:

  • LC Project no.: T-22348A
  • LC Certificate no.: LC22348-1
  • LC Listing Report no.: 11.03.22348-1_Rev A
Go to Top