Certification Record
LC1253096
Caron Measurement and Controls Ltd.
2026-09-15
Alberta
Canada
CMC-ELM-TMR-00-XX, CMC-ELM-TMR-MD-XX, CMC-ELM-TMR-AC1D, CMC- ELM-MSXP
33.160.01; 35.020
- Eliminator Programmable Controllers (Explosion Proof) Series
- Model Nos.: CMC-ELM-TMR-00-XX, CMC-ELM-TMR-MD-XX, CMC-ELM-TMR-AC1D, CMC-
ELM-MSXP - Ratings:
- Class I, Division 1, Group D T4A;
- Class I, Zone 1 Ex db IIA, IIB T4A/T5 Gb;
- Hazardous locations in an ambient temperature range of -40°C to +40°C.
- Type 4X.
- With Motor Control Board (CMC-ELM-TMR-AC-1D, CMC-ELM-TMR-MD-XX, CMC-ELM-000-MDXX) – Round Enclosures, (CMC-ELM-TMR-AC-1D includes square enclosure and does not necessarily require -40°C)
-
- Hazardous Location Ratings:
- Class I, Division 1, Group D T4A; Class I, Zone 1 Ex db IIA, IIB T4A Gb;
- Type 4X
- Ambient Temperature: -40°C ≤ Tamb ≤ 40°C
- Electrical Ratings: Voltage: 10-30 VDC, Max Cont. Current: 20A.
- Hazardous Location Ratings:
- 2. Without Motor Control Board (CMC-ELM-TMR-00-XX, CMC-ELM-MSXP, CMC-ELM-MSXPW)
-
- Hazardous Location Ratings:
- Class I, Division 1, Group C, D T5; Class I, Zone 1 Ex db IIA, IIB T5 Gb;
- Type 4X
- Ambient Temperature: -40°C ≤ Tamb ≤ 40°C
- Electrical Ratings: Voltage: 9-30 VDC, Max Cont. Current: 2A
- Hazardous Location Ratings:
- 3. CMC-ELM-MSXPW
-
- Hazardous Ratings:
- Class I, Division 1, Group C, D T5; Class I, Zone 1 Ex db IIA, IIB T5 Gb;
- Type 4X
- Ambient Temperature: -40°C ≤ Tamb ≤ 40°C
- Electrical Ratings: Voltage: 6-30 VDC, Max Cont. Current: 2A
- Hazardous Ratings:
- CSA C22.2 No. 14-18 (R2022) – Industrial Control Equipment
- UL 508, Edition 18 – Industrial Control Equipment
- CSA C22.2 No. 30:20 – Explosion Proof Equipment
- CSA C22.2 No. 60079-0:2019 – Explosive atmospheres – Part 0: Equipment – General requirements
- CSA-C22.2 No. 60079-1:16 (R2021) – Explosive atmospheres – Part 1: Equipment protection by flameproof enclosures “d”
- UL 1203 – Edition 5 – Explosion Proof and Dust-Ignition Proof Electrical Equipment for use in Hazardous (Classified) Locations
- UL60079-0 – Edition 7 – Standard for Explosive atmospheres – Part 0: Equipment – General Requirements.
- UL 60079-1 – Edition 7 – Standard for Explosive Atmospheres – Part 1: Equipment Protection by Flameproof Enclosures.
- The approved construction of the labelled product is as described below in this report.
- Certification is voided if the labeled product has been modified or changed by the manufacturer or end user after labeling.
- Certification covers only safety from electric shock and fire/explosion hazards and apply only to the construction elements described in this report.
- LC did not evaluate the suitability of the use of equipment involving toxic or corrosive gases; steam locations defined as hazardous locations by the Canadian Electrical Code or the National Electrical Code.
General Note:
- LC Project no.: T-22348A
- LC Certificate no.: LC22348-1
- LC Listing Report no.: 11.03.22348-1_Rev A