LC Clients

Certification Record

LC1234957
Northridge Electric Inc.
2026-09-29
Ontario
Canada
14438
21.180, 29.260.20
  • Explosion Proof Starter Panel
  • Model Number: 14438
  • Ratings
    • 230 Vac, 3 Phase, 15 Amps, 60Hz
    • Class I, Division 1, Group D, T3
    • -40°C <Tamb<+35°C

Serial No.:

Panel Serial Number LabTest Label number
NOR-14438F C-20185
NOR-14438L C-20186
NOR-14438G C-20187
NOR-14438M C-20188
NOR-14438H C-20189
NOR-14438E C-20190
NOR-14438J C-20191
NOR-14438I C-20192
NOR-14438K C-20193
  • CSA C22.2 No. 30:20
  • CSA C22.2 No. 286:17*

*Compliance was accepted from the QPS evaluation report number LPS124-1

  • All unused device openings must be fitted with a certified close-up plug.
  • All cable glands used in the device must be of certified Class I, Division 1 cable glands.
  • The end user is to ensure appropriate earthing upon installation.
  • Power input and output (I/O) wiring shall be accordance with Class 1, Division 1 wiring method per the Canadian Electrical Code for installation within Canada.
  • Cables must be effectively clamped to prevent pulling or twisting.
  • Customers will be responsible for maintaining the temperature inside the explosion proof chamber above -20°C.
  • The enclosure shall not be open when the explosive atmosphere is present.

General Note:

  • LC Project no.: 26-6765
  • LC Unit Verification Certificate no.: LC26-6765-1
  • LC Unite Verification Report no.: 11.03.26-6765-1_Rev 0
Go to Top