Certification Record
- 5KVA Power Unit
- OPVAT/XXX/X/XXXX/X/XXXX/XXX/XXXX/XXX/XXX/XX/X
(reference model nomenclature) - Model Nomenclature:
OPVAT/XXX/X/XXXX/X/XXXX/XXX/XXXX/XXX/XXX/XX/X
OPVAT/ Indicates the product is one of the Oil Processing 5kVA Variac Power Units
/XXX/ (1st 3 numbers) = kVA Size
005 = 5kVA/X/ (next letter) = Input phase & frequency
C=single phase 60 Hz/XXXX/ (next 4 numbers) = Input primary voltage
0440 = 440V
0460 = 460V
0480 = 480V
0600 = 600V/X/ (next letter) = Output type
D= DC/XXXX/ (next 4 numbers) = Output voltage (highest voltage tap will be listed)
50X0 = 50kV/XXX/ (next 3 digits) =Tank material and finish
316 = 316 Stainless steel (with enamel finish and SS Accessories are included)
MEG = Steel with Megatran 50 three coat paint system
PDR = Powder Coat System/XXXX/ (next 4 numbers) = Output flange NPT size or weld neck flange size and weight
2150= 2” 150Lb weld neck flange/XXX/ (next 3 letters) = Tank coolant type
MIN = Cross Trans 206 Mineral Oil
SIL = Dow Xiameter PMX-561 Silicone Fluid/XXX/ (next 3 numbers) = Tertiary winding voltage
120 = 120vac Tertiary winding/XX/ (next 2 letters) = Optional Sunshield
SS = Sunshield included
NA = No Sunshield/X/ (last letter) = Stainless Steel or Brass accessories (PRV / Drain Valve)
S= Stainless Steel Accessories (Premium)
B= Brass Accessories (Standard) - Ratings:
- Input:
- 440 / 460 / 480 / 600Vac
- 4 / 10.8 / 10.4 / 8.3 Amps
- 60Hz
- 100% Reactance
- Output:
- 0 – 50KVDC, 0.1ADC (0.14ADC PK)
- Ex ec oc IIC T4 Gc
- AEx ec oc IIC T4 Gc
- Class I, Zone 2
- -40°C to 50°C
- NEMA 4 / IP66
- Input:
- UL 60079-0 (Ed.7.0) Explosive atmospheres-Part 0: Equipment – General requirements
- UL 60079-6 (Ed.4.0) Explosive atmospheres-Part 6: Equipment protection by liquid immersion “o”
- UL60079-7 (Ed.5.1) Explosive atmospheres-Part 7: Equipment protection by increased safety “e”
- UL 1012 (Ed.8.0) Power Units Other Than Class 2
- CAN/CSA C22.2 No. 60079-0:19 (R2024) Explosive atmospheres-Part 0: Equipment – General requirements
- CAN/CSA C22.2 No. 60079-6:17 (R2022) Explosive atmospheres-Part 6: Equipment protection by liquid immersion “o”
- CAN/CSA C22.2 No. 60079-7:16 (R2021) Explosive atmospheres-Part 7: Equipment protection by increased safety “e”
- CAN/CSA C22.2 No. 107.1:16 (R2021) Power conversion equipment
- When connecting the equipment to a source of supply and other connections, the installer shall ensure that the entry method into the equipment maintains a degree of protection of at least IP65.
- All incoming cables shall be fitted with appropriately sized ring crimp connections when connecting to a source of supply.
- The oil tank level gauges shall be inspected for any damage, aging, cracks, etc, and be verified to be operating properly at least annually.
- The oil level in the oil tanks must always be within the minimum and maximum allowed fill levels.
- Field wiring to L1/L2 must be rated for at least 90°C.
- Field wiring to all other input terminals must be rated for at least 90°C.
- Covers and lids shall be closed and secured by all fasteners whenever the equipment is energized.
- The Internal liquid level switch circuit must be used, and it must be wired into a Sil 1 or PLc rated safety circuit when operated.
- The Lid mounted pressure switch must be connected to a suitably rated SIL-1 (or better) controller that automatically de-energizes all power to the equipment if the pressure rises above a maximum specified level.
- If this unit needs to have its oil changed or needs to have oil added to it and Cross Grade 206 oil is not available, other equivalent oils are acceptable to be used only if they 1) meet the IEC296 / IEC60296 standards and 2) hold equivalent or better parameter specification. If the unit uses Dow Corning Silicone Fluid, then only Dow Corning Silicone Fluid may be used as a replacement fluid; no substitutions are allowed.
General Note:
- Listing Report no. 11.02.25-5654-1_Rev.0