LC Clients

Certification Record

21800
RIC Electronics Ltd.
2015-04-08
British Columbia
Canada
MX System and MX Stack System Components
29.240.30
Modular Inverter System Components
Model/Ratings:  
MX System and MX Stack System Components:
 Rated (nominal) input voltages: 12(13.4), 24(27.6), 32(36.8), 48(55.2), 66(75.9), 108(124) VDC
 Rated output per MX Power Module: 117VAC, 8.5Amps, 1000Watts, 50/60Hz
  • Included Recognized Components: MX System, MX Stack System, MX Cage, MX Alarm Card and MX Transfer Switch, MX Control Card, MX System Monitor II, and MX Power Module. 
Model Number designations per recognized components are as follows: 
MX Stack System Part Number 117VAC Only 
Model Number: S (A) (B) (C) (D) R(X) (F)(F) (G)(G) (H) (I) (J)(J) 
(A) = Phases:  1=Single Phase ; 2=Bi-Phase ; 3=3-Phase
(B) = Cage Size:  1=19" ; 2=23"
(C) = System Type:  A=Monitoring Module & CC ; B=Master Module 
(D) = Monitoring Module:  A=Alarm Card ; C=Sys Mon II ; X=Transfer SW
(X) = Monitoring Module:  2 digit option code
(F) = Control Card, Master Module Per Phase:  **=No CC ; C*=1 CC ; CC=2 CC ; 1MM=M*
(G) = Number of Power Modules Per Phase: 01 to 21 (use ** for no PM)
(H) = DC Voltage:  1=12V ; 2=24V ; 3=32V ; 4=48V ; E=66V ; I-108V
(I) = Frequency:  5=50Hz ; 6=60Hz ; 1=100Hz ; 4=400Hz
(J) = Option Code:
  • 07=Conformal Coating
  • 08=Low Idle Current
  • 15=Delete a phase from 3-phase, 117/208VAC split phase
  • 17=1 extra expansion cage per phase
  • 18=2 extra expansion cages per phase
  • 21=Add accessory through extra Sales Order line item
  • 36=1 extra expansion cage per phase and Low Idle
  • 37=1 extra expansion cage per phase with relay rack
  • 40=Conformal coating and  Low Idle Current
  • 43=1 extra expansion cage per phase & accessory through extra Sales Order line item
  • 45=Low I, Conformal, and Accessory
  • 47=Conformal & Accessory
  • 52=Add Customer Interface Cage
  • 54=Add Customer Interface Cage & accessory through extra Sales Order line item
  • 55=2 extra expansion cages per phase & accessory through extra Sales Order line item
  • 59=Remove customer interface cage
  • 60=Sys Mon II and Transfer Switch
  • 66=Delete a phase from 3-phase, 117/208VAC split phase & accessory through extra Sales Order line item
  • 70=1 extra expansion cage per phase & add customer interface cage
  • 73=2 extra expansion cages per phase, customer interface cage & accessory through extra Sales Order line item
  • 74=1 extra expansion cage per phase, customer interface cage & accessory through extra Sales Order line item
  • 78=23" System w/ 19" BP – 3.2" Accessory
  • 79=1 extra expansion cage per phase, No customer interface, accessory through extra Sales Order line item
  • 81=1 extra expansion cage per phase, No customer interface 
  • 82=19" System w/ 16" BP – 3.2" Monitoring Module & 2.8" Accessory  
  • 83=19" System w/ 16" BP – 2.8" Monitoring Module & 3.2" Accessory
  • 86=Delete a phase from 3-phase, 117/208VAC split phase, 1 extra expansion cage per phase
  • 87=19" System w/ 16" BP in A-cage, (opt 82 cage) 1 extra expansion cage per phase
  • 90=19" System w/ 60 option A-cage, 3.2" wide accessory through extra Sales Order line item
  • 91=19" System w/ 16" BP (82 option cage), Add 5kw XFR BP w/ mechanical transfer switch
  • 92=19" cage w/ 16" back plane, has System Monitor Card II (M83), accessory through extra Sales Order line item   
 Example:
  • 23" 48VDC, 117/208VAC 3-Phase, 60Hz 8kW N+1 Redundant, Sys Mon II w/ SNMP V3 = S32ACR6CC094600
 

CSA C22.2 NO. 107.1-01 (R2011) – General Use Power Supplies
UL 1778: 2014 (Ed. 5) – Uninterruptible Power Systems

Indoor Use Only.
Listed as a component of other Listed equipment where the suitability of the combination is to be determined by the Authority Having Jurisdiction.

Go to Top