Certification Record
LC1229533
Eaton Crouse-Hinds
2016-08-30
New York
United States
SSP-3421P/2P/3P-250
29.260.20
Ø Electrical Distribution Panel
Ø Catalog No.: SSP-3421P/2P/3P-250
Ø Ratings:
480Vac max, 250A, 60Hz
Class I Zone 2 AEx nA IIC Gc T4 -20°C ≤ Ta ≤ +55°C
Class I Zone 2 AEx nA IIB Gc T4 -40°C ≤ Ta ≤ +55°C for breaker model GHG62x1 and GHG62x2
Class I Division 2 Group A B C D
Ex nA IIC T4 Gc -20°C ≤ Ta ≤ +55°C
Ex nA IIB T4 Gc -40°C ≤ Ta ≤ +55°C for breaker model GHG62x1 and GHG62x2C
CAN / CSA – C22.2 No. 29 – M1989 (R2004) ;
UL 67 (Ed.12):2009 ;
CAN / CSA – C22.2 No.60079 – 15:2012 ;
UL 60079 – 15 (Ed.4):2013
Intended to be used in ambient temperature of -40A°C to +55A°C for breaker model GHG62x1 and GHG62x2.
Intended to be used in ambient temperature of -20A°C to +55A°C for breaker model GHG62.