LC Clients

Certification Record

LC1230773
Eco Heating Systems Groningen B.V.
2017-12-21
Groningen
Netherlands
CB-299-CH, CB-399-CH, CB-499-CH
97.100.20, 27.060.01
  • Hot Water Supply Boiler
  • Model Nos.: CB-299-CH, CB-399-CH & CB-499-CH
  • Ratings: See below
  • Model CB-299-CH CB-399-CH CB-499-CH
    MIN MAX MIN MAX MIN MAX
    NG MBTU/HR 109 295 80 396 98 474
    LP MBTU/HR 110 294 80 397 98 473
    Fan Speed (RPM) 2500 6450 1800 6700 (NG)

    6700 (LP)

    2000 7650 (NG)

    7400 (LP)

    AFUE (%) per CAN/CSA-P.2-2013 95 NA NA
    Combustion Efficiency (%) per ANSI Z21.13/CSA 4.9-2017 NA NA 88.5 NA 88.6
    Combustion Efficiency (%) per ANSI/AHRI 1500-2015 NA NA 93.7 NA 94.7
    Electrical: 120 VAC, 60 Hz, less than 12 Amp

     

  • ANSI Z21.13-2017/ CSA 4.9-2017
  • CSA-2.17-2017
  • CAN/CSA-P.2-13
  • Suitable for use with Natural Gas or Propane, for indoor use only.
  • Not to be used with solid fuel.
  • The ventilation of the boiler room must meet local and national standards and regulations, regardless of the selected supply of fresh air to the boiler.
  • The flue gas system must be per the Installation manual.
  • Unit must be installed with a certified pressure relief valve supplied by the manufacturer and installed per Installation manual.
  • Project No.: 16309
  • Certificate No.: 16309-2G
Go to Top