Certification Record
LC1230691
A.B. Controls and Technology Inc.
2019-09-23
Texas
United States
IOM SX-OP
29.260.20
- Products:
– Type SX Enclosure
– Model No: IOM SX-OP - Ratings:
Type SX enclosure evaluated and conforms to below ratings for hazardous location with fiber optics components installed inside the enclosure which also complies to the following ratings:
Ratings for Type SX Enclosure | |
Ex eb op is IIC T5 Gb | Class I, Zone 1, AEx eb op is IIC T5 Gb |
Ex ib op is IIC T5 Gb | Class I, Zone 1, AEx ib op is IIC T5 Gb |
Ex ia op is IIC T5 Ga | Class I, Zone 1, AEx ia op is IIC T5 Ga |
Ex op is IIC T5 Ga | Class I, Zone 1, AEx op is IIC T5 Ga |
Ex eb op pr IIC T5 Gb | Class I, Zone 1, AEx eb op pr IIC T5 Gb |
Ex ib op pr IIC T5 Gb | Class I, Zone 1, AEx ib op pr IIC T5 Gb |
Ex ia op pr IIC T5 Gb | Class I, Zone 1, AEx ia op pr IIC T5 Gb |
Ex op pr IIC T5 Gb | Class I, Zone 1, AEx op pr IIC T5 Gb |
Class I Division 2 Group A, B, C, D | |
-50˚C≤Ta≤55 ˚C; IP66 |
- CAN/CSA-C22.2 No. 60079-0:15 / UL-60079-0 (Ed. 6)
- CAN/CSA-C22.2 No. 60079-7:16 / UL-60079-7 (Ed. 5)
- CAN/CSA-C22.2 No. 60079-11:14 / UL-60079-11 (Ed. 6)
- CAN/CSA-C22.2 No. 60079-28:16 / UL-60079-28 (Ed. 2)
- C22.2 NO. 213-17 / UL121201 Ed. 9
- UL 508A (Ed. 3) and C22.2 No. 286-17
- The Type SX range of junction boxes shall be installed with components which are approved for the application and the suitable hazardous environment.
- The SX range of junction boxes are fitted with an arrangement of suitably certified terminals. Before the junction box is installed, its total power for particular application will be calculated in accordance with EN 60079-7, Annex E, E.2 and will not exceed the values given in the table below:
SX Ref | EPL | Max. Power Dissipation
Calculated for T5 at maximum Ta of 55˚C |
SX0 | Ga, Gb | 19 |
SX1 | Ga, Gb | 29 |
SX2 | Ga, Gb | 36 |
SX3 | Ga, Gb | 42 |
SX4 | Ga, Gb | 44 |
SX5 | Ga, Gb | 50 |
SX6 | Ga, Gb | 57 |
SX7 | Ga, Gb | 68 |
SX8 | Ga, Gb | 119 |
SX225 | Ga, Gb | 359 |
SX45 | Ga, Gb | 8 |
SX64 | Ga,Gb | 10 |
SX66 | Ga,Gb | 114 |
Optical Power | |
op pr’ applications | op is’ applications |
When ‘op pr’ is used, the splice case is limited to 100mW and a -40ºC to 60ºC ambient temperature. | When ‘op is’ is used for T5 class to a maximum irradiance of 5 mW/mm2 (surface area not exceeding 400 mm2) and Signal power is limited to 15 mW@T5. |
- Project No. LV-14757
- Report No. 14757-1S_Rev0