LC1230217
Emerson Process Management Valve Automation Inc.
2019-12-10
Texas
United States
CM-64, FL-40, FQ-10, FQ-20, FQ-30, FQ-50, CL-25
29.020, 29.260.20
  • Rotary Electric Actuator
  • Model Nos.: CM-64, FL-40, FQ-10, FQ-20, FQ-30, FQ-50, CL-25
  • 90 – 240Vac, 50/60Hz, 2.9 Amps max (for models CM-64, FL-40, FQ-10, FQ-20, FQ-30, FQ-50, CL-25)
  • 24Vdc, 4.6A (for models CM-64, FQ-10, FQ-20, CL-25)
  • Class I Zone 1 Ex db eb IIC T4 (T6) Gb
  • Class I Zone 1 AEx db eb IIC T4 (T6) Gb
  • -40˚C ≤ Ta ≤ 60˚C (temperature class T4)
  • -40˚C ≤ Ta ≤ 40˚C (temperature class T6)
  • CSA-C22.2 No. 14-13
  • CSA-C22.2 No. 60079-0:15
  • CSA-C22.2 No. 60079-1:16
  • CSA-C22.2 No. 60079-7:16
  • UL 508:2007 (Ed. 17)
  • UL 60079-0:2013
  • UL 60079-1:2015
  • UL 60079-7:2016 (Ed. 5)
  • The yield stress of the screws for the flameproof enclosure must exceed 400 N/mm2
  • Units shall be provided with protection for the output cable after it leaves the enclosure depending upon installation Hazardous Location Area Classification of the surrounding environment. The protection should be provided as per instructions of NFPA 70: National Electrical Code for US and C22.1 Canadian Electrical Code for Canada. The protection shall not interfere with explosion proof design of the unit
  • General standard temperature class T4:
    Ambient temperature -20˚C to +60˚C or -40˚C to +60˚C
    The protection device/temperature limiter S-125 has the response temperature of 130˚C
  • Special design with temperature class T6:
    Ambient temperature -20˚C to +40˚C or -40˚C to +40˚C
    The protection device/temperature limiter SF76E has the response temperature of 76˚C
  • Project No. LV-14874
  • Certificate No. 16420-1S-ML2 Rev1