Certification Record
LC1230773
King Heating Products Inc.
2019-04-01
British Columbia
Canada
HWB-299, HWB-399, HWB-499
97.100.20; 27.060.01
- Instantaneous or Circulating Tank Water Heater
- Model Nos.: HWB-299, HWB-399, HWB-499
- Ratings: See below
Model (Heat Exchanger and Boiler Type) | 7+3 | 10+6 | 12+6 | |||
HWB-299 | HWB-399 | HWB-499 | ||||
MIN | MAX | MIN | MAX | MIN | MAX | |
NG MBTU/HR | 60 | 295 | 80 | 396 | 98 | 474 |
LP MBTU/HR | 60 | 294 | 80 | 397 | 98 | 473 |
Fan Speed (RPM) | 1600 | 6450 | 1800 | 6700 (NG)
6700 (LP) |
2000 | 7650 (NG)
7400 (LP) |
Thermal Efficiency (%) per ANSI Z21.10.3-2015-CSA 4.3-2015 | 96.8 (NG)
95.5 (LP) |
95.6 (NG)
95.8 (LP) |
97.4 (NG)
95.4 (LP) |
|||
Electrical: 120 VAC, 60 Hz, less than 12 Amp |
- ANSI Z21.10.3 – 2015 / CSA 4.3 – 2015
- CSA-2.17-2017
- Suitable for use with Natural Gas or Propane, for indoor use only.
- Not to be used with solid fuel.
- The ventilation of the boiler room must meet local and national standards and regulations, regardless of the
selected supply of fresh air to the boiler. - The flue gas system must be per the installation manual.
- Unit must be installed with a certified pressure relief valve supplied by the manufacturer per instructions manual.
- Water pipes must be approved material for potable water.
GENERAL NOTES
- Refer to LabTest Report No. 16309-1G_Rev 2 (Eco Heating Systems Groningen B.V.)