Certification Record
LC1224834
A.B. Controls and Technology
2023-05-01
Texas
Canada
EJB-C
29.260.20, 29.240.30, 29.240.30, 25.040.40
- Enclosure
- Model No.: EJB-C
- Ratings:
- Class I, Zone 1
- AEx db [ia Ga] IIB + H2 T6 Gb
- Ex db [ia Ga] IIB + H2 T6 Gb
- Ta: -25°C to +60°C
Input: Output:
Ui = 27.5V Uo = 27.5V
Ii = 114 mA Io = 114 mA
Ci = 58 nF Po = 784 mW
Li = 831 μH Co = 25 nF
Pi = 784 mW Lo = 1.9mH
- UL 508A Ed. 3
- UL 60079-0:2019
- UL 60079-1:2015
- UL 60079-11:2013
- CSA C22.2 No. 286-17
- CSA C22.2 No. 60079-0:2019
- CSA C22.2 No. 60079-1:2015
- CSA C22.2 No. 60079-11:2014
- A separation of at least 50mm must be maintained between different intrinsically safe cables/wires and intrinsically safe cables/wires and non-IS cables all the time.
- Cable systems for wiring of intrinsically safe explosive atmospheres shall be installed to minimize migration of flammable fluids to other locations.
- No changes to or modifications of the intrinsically safe devices are permitted without additional assessment.
- Only approved certified cable gland and conduit sealing fitting shall be used.
- All unused device openings must be fitted with a certified close-up plug. The end user is to ensure appropriate earthing upon installation.
General Note:
- Project no.: LV-15957
- LC Listing Report no.: 11.02.15957-1_Rev 0
- LC Certificate no.: LC15957-1