Certification Record
- Oil Processing Power Supply
- Ratings:
- Input: 380 – 690Vac, 50-60Hz, 1 phase, 15-300kVA or 2400 – 6600Vac, 50-60Hz, 1 phase, 50-300kVA
- Output: AC units = 8 – 25KVAC DC units = 12 – 25KVDC DC units 251KVA or higher = 16.5 – 25KVDC
- IP 66 / NEMA 4X
- Ex ec oc IIC T5 Gc
- AEx ec oc IIC T5 Gc
- Class I Zone 2
- -40°C to +55°C
- IP6
Model Nomenclature:
Model: OP/XXX/X/XXXX/X/XXXX/XXX/XXXX/XX/XX/XX/XX/XX/X/X
Where:
OP/ Indicates the product is one of the Oil Processing product line
/XXX/ (1st 3 numbers) = kVA Size (any range from 015kVA to 300kVA)
/X/ (next letter) = Input phase & frequency (C=single phase 60 Hz, G=single phase 50 Hz)
/XXXX/ (next 4 numbers) = Input primary voltage (any range from 0380 to 6600V)
/X/ (next letter) = Output type (A=AC, D=DC)
/XXXX/ (next 4 numbers) = Output voltage (highest voltage tap will be listed Ex. 12X0 = 12Kv, 25X0 = 25kV, 16X5 = 16.5kV, 08X5 = 8.5kV etc. Acceptable tap voltage range must be between 8kvAC – 25kvAC on AC units, 12kvDC – 25kvDC on DC units, 16.5kvDC – 25kvDC on DC units 251kVA and up
/XXX/ (next 3 digits) =Tank material and finish 316= 316 Stainless steel (with enamel finish and SS Accessories are included) MEG= Steel with Megatran 50 three coat paint system PDR= Powder Coat System
/XXXX/ (next 4 numbers) = Output flange NPT size or weld neck flange size and weight 1NPT= 1” NPT weld flange 2NPT= 2” NPT weld flange 3NPT= 3” NPT weld flange 2150= 2” 150Lb weld neck flange 4150= 4” 150Lb weld neck flange 4300= 4” 300Lb weld neck flange 6150= 6” 150Lb weld neck flange 6300= 6” 300Lb weld neck flange 8150= 8” 150Lb weld neck flange 8300= 8” 300Lb weld neck flange
/XX/ (next 2 letters) = Internal Junction Box mounted Pressure Transmitter options PT = Pressure Transmitter or NA = No transmitter
/XX/ (next 2 letters) = Internal Junction Box mounted Temperature Transmitter options TT = Temperature Transmitter or NA = No transmitter
/XX/ (next 2 numbers) = Tertiary winding voltage 100 = 100vac Tertiary winding or 120 = 120vac Tertiary winding
/XX/ (next 2 letters) = Optional Sunshield (SS = Sunshield included, NA = No Sunshield)
/XX/ (next 2 letters) = Optional Bellows (BW = Bellows included, NA = No Bellows)
/X/ (single number) = CT secondary current rating (1= 1AMP CT secondary, 5= 5AMP CT secondary)
/X/ (last letter) = Stainless Steel or Brass accessories (PRV / Drain Valve) S= Stainless Steel Accessories (Premium) or B= Brass Accessories (Standard)
- UL 60079-0; Edition 7
- UL 60079-6; Edition 4
- UL 60079-7; Edition 5
- UL 1012; Edition 8
- CAN/CSA C22,2 No. 60079-0; 2020
- CAN/CSA C22,2 No. 60079-6; 2022
- CAN/CSA C22,2 No. 60079-7; 2017
- CAN/CSA C22,2 No. 107.1; 2021
- When connecting the equipment to a source of supply and other connections, the installer shall ensure that the entry method into the equipment maintains a degree of protection of at least IP66.
- All incoming cables shall be fitted with appropriately sized ring crimp connections when connecting to a source of supply.
- The oil tank level gauges shall be inspected for any damage, aging, cracks, etc. and be verified to be operating properly at least annually.
- The oil level in the tank must always be within the minimum and maximum allowed fill levels.
- Field wiring to L1 and L2 must be rated for at least 90o
- Field wiring to all other input terminals in the terminal enclosure must be rated for at least 90o
Covers and lids shall be closed and secured by all fasteners whenever the equipment is energized.
- The output HV tap switch must only be operated when the equipment is de-energized/ the handle must be locked whenever the equipment is in use.
- The internal pressure switch circuit must be used, and it must be wired into a Sil 1 or PLc rated safety circuit and must be connected to circuitry that will automatically disconnect power to the system.
- If this unit is to have its oil changed or need to have oil added to it and Cross Grade 206 oil is not available, other equivalent oils are acceptable to be used only if they 1) meet the IEC296 / IEC 60296 standards and 2) hold equivalent or better parameter specification.
General Note:
- Project no.: LV-15887A
- LC Listing Report no.: 11.02.15887-1_Rev.0
- LC Certificate no.: LC15887-1