Certification Record
                    LC1230217                
            
                    Emerson Process Management Valve Automation Inc.                
            
                    2019-12-10                
            
                    Texas                
            
                    United States                
            
                    CM-32, FL-05, FL-15, FL-25, FQ-03, FQ-06, CL-05, CL-15                
            
                    29.020, 29.260.20                 
            - Rotary Electric Actuator
 - Model Nos.: CM-32, FL-05, FL-15, FL-25, FQ-03, FQ-06, CL-05, CL-15
 - 90 – 240Vac ±10%, 50/60Hz, IN=2A / 230Vac
 - 20 – 30Vdc, 5.5A, IP67
 - Class I Zone 1 Ex db eb IIC T4 (T6) Gb
 - Class II Zone 21 Ex tb IIIC T4 Db
 - Class I Zone 1 AEx db eb IIC T4 (T6) Gb
 - Class II Zone 21 AEx tb IIIC T4 Db
 - -40˚C ≤ Ta ≤ 60˚C (temperature class T4)
 - -40˚C ≤ Ta ≤ 40˚C (temperature class T6)
 
- CSA-C22.2 No. 14-13
 - CSA-C22.2 No. 60079-0:15
 - CSA-C22.2 No. 60079-1:16
 - CSA-C22.2 No. 60079-7:16
 - CSA-C22.2 No. 60079-31:15
 - UL 508:2007 (Ed. 17)
 - UL 60079-0:2013
 - UL 60079-1:2015
 - UL 60079-7:2016 (Ed. 5)
 - UL 60079-31:15
 
- The yield stress of the screws for the flameproof enclosure must exceed 400 N/mm2
 - Flameproof Control and Motorbox “d” shall always be assembled with the oil filled gearbox
 - General standard temperature class T4:
Ambient temperature -20˚C to +60˚C or -40˚C to +60˚C
The protection device/temperature limiter S-125 has the response temperature of 130˚C - Special design with temperature class T6:
Ambient temperature -20˚C to +40˚C or -40˚C to +40˚C
The protection device/temperature limiter SF76E has the response temperature of 76˚C - Project No. LV-14874
 - Certificate No. 13198-1S-ML1 Rev3