LC Clients

Certification Record

LC1230217
Emerson Process Management Valve Automation Inc.
2019-12-10
Texas
United States
CM-32, FL-05, FL-15, FL-25, FQ-03, FQ-06, CL-05, CL-15
29.020, 29.260.20
  • Rotary Electric Actuator
  • Model Nos.: CM-32, FL-05, FL-15, FL-25, FQ-03, FQ-06, CL-05, CL-15
  • 90 – 240Vac ±10%, 50/60Hz, IN=2A / 230Vac
  • 20 – 30Vdc, 5.5A, IP67
  • Class I Zone 1 Ex db eb IIC T4 (T6) Gb
  • Class II Zone 21 Ex tb IIIC T4 Db
  • Class I Zone 1 AEx db eb IIC T4 (T6) Gb
  • Class II Zone 21 AEx tb IIIC T4 Db
  • -40˚C ≤ Ta ≤ 60˚C (temperature class T4)
  • -40˚C ≤ Ta ≤ 40˚C (temperature class T6)
  • CSA-C22.2 No. 14-13
  • CSA-C22.2 No. 60079-0:15
  • CSA-C22.2 No. 60079-1:16
  • CSA-C22.2 No. 60079-7:16
  • CSA-C22.2 No. 60079-31:15
  • UL 508:2007 (Ed. 17)
  • UL 60079-0:2013
  • UL 60079-1:2015
  • UL 60079-7:2016 (Ed. 5)
  • UL 60079-31:15
  • The yield stress of the screws for the flameproof enclosure must exceed 400 N/mm2
  • Flameproof Control and Motorbox “d” shall always be assembled with the oil filled gearbox
  • General standard temperature class T4:
    Ambient temperature -20˚C to +60˚C or -40˚C to +60˚C
    The protection device/temperature limiter S-125 has the response temperature of 130˚C
  • Special design with temperature class T6:
    Ambient temperature -20˚C to +40˚C or -40˚C to +40˚C
    The protection device/temperature limiter SF76E has the response temperature of 76˚C
  • Project No. LV-14874
  • Certificate No. 13198-1S-ML1 Rev3
Go to Top